Practice test

Electrician Practice Exam 12

Advanced electrician practice exam on conductor ampacity derating, feeder sizing, motor circuits, and grounding under the NEC. 25 timed questions explained.

Free preview

These questions are for study practice only and are not official exam questions.

Question 1

1

A 480Y/277 V feeder supplies a 100 A continuous lighting load and a 60 A noncontinuous load. What minimum feeder conductor ampacity is required before derating?

Question 2

2

Four THHN conductors share a raceway in a 40 C ambient. An 8 AWG copper has a 90 C ampacity of 55 A. After the 40 C correction (0.91) and the 80% adjustment for 4 conductors, the adjusted ampacity is about:

Question 3

3

A 400 A service has parallel 250 kcmil copper per phase. Per NEC Table 250.66, what minimum copper grounding electrode conductor is required?