Practice test
Florida Journeyman Electrician Practice Test
Free Florida journeyman electrician practice test with 20 NEC-based questions. Covers grounding, load calculations, and wiring methods. Instant scoring.
These questions are for study practice only and are not official exam questions.
Question 1
Question 2
Which NEC term describes the conductive connection that joins together metal parts of an electrical system to establish electrical continuity, but is NOT intended to carry fault current to earth?
Question 3
The NEC informational notes recommend limiting voltage drop on a branch circuit to what maximum percentage for satisfactory equipment operation?
Question 4
A 240V, single-phase motor has a full-load current (FLC) of 18A. Using NEC Table 430.52, what is the maximum rating of an inverse-time circuit breaker permitted as the branch-circuit short-circuit and ground-fault protective device?
Question 5
What is the primary purpose of equipment grounding in an electrical system?
Question 6
Interior metal gas piping in a residence must be bonded. To which of the following is it permitted to be bonded per NEC 250.104(B)?
Question 7
When calculating the general lighting load for a dwelling using the NEC standard method, what unit load (VA per square foot) is applied to the gross floor area?
Question 8
The NEC requires AFCI protection for 15A and 20A, 120V branch circuits in dwelling units. Which areas of the dwelling are covered by this requirement?
Question 9
A 20A, 120V branch circuit supplies a single receptacle. What is the maximum continuous load that may be placed on this circuit per NEC requirements?
Question 10
GFCI protection is required for all 15A and 20A, 125V receptacles located in which of the following locations?
Question 11
When applying the NEC optional calculation method for a single-family dwelling service, all load above the first 10 kVA is multiplied by what percentage?
Question 12
A feeder supplies four electric ranges with nameplate ratings of 12 kW each. Using NEC Table 220.55, what is the maximum demand load (in kW) for these four ranges?
Question 13
A concrete-encased electrode (Ufer ground) must consist of at least how many feet of bare copper wire or steel rebar encased in concrete near the bottom of a foundation footing?
Question 14
A 2,400 sq ft dwelling has a 12 kW electric range, a 5.5 kW water heater, a 5 kW dryer, a 3-ton central A/C with a 28A/240V nameplate, and a 10 kW electric heat strip. The A/C and heat strip cannot operate simultaneously. Per NEC 220.60, which load is included in the service calculation?
Question 15
A metal water pipe enters a building and is used as a grounding electrode. According to the NEC, what is the minimum length of metal water pipe that must be in contact with the earth for it to qualify as a grounding electrode?
Question 16
What is the color marking required by the NEC for a grounded conductor (neutral) of sizes 6 AWG and smaller?
Question 17
In a residential service, where is the first and only permitted point at which the neutral (grounded conductor) and the equipment grounding conductor may be connected together?
Question 18
A dwelling unit has a gross floor area of 1,800 sq ft. Using the NEC standard method, what is the general lighting load in VA before any demand factors are applied?
Question 19
In a standard residential load calculation, what demand factor is applied to a single electric clothes dryer in a single dwelling unit?
Question 20
A 480/277V, 3-phase, 4-wire wye service uses 500 kcmil copper ungrounded conductors. According to NEC Table 250.66, what is the minimum size copper grounding electrode conductor required?
Enable JavaScript for the interactive step-by-step quiz with instant scoring and explanations.