Practice test
Florida Journeyman Electrician Practice Test
Free Florida journeyman electrician practice test with 20 NEC-based questions. Covers grounding, load calculations, and wiring methods. Instant scoring.
These questions are for study practice only and are not official exam questions.
Question 1
Question 2
Which NEC term describes the conductive connection that joins together metal parts of an electrical system to establish electrical continuity, but is NOT intended to carry fault current to earth?
Question 3
What is the color marking required by the NEC for a grounded conductor (neutral) of sizes 6 AWG and smaller?
Question 4
In a residential service, where is the first and only permitted point at which the neutral (grounded conductor) and the equipment grounding conductor may be connected together?
Question 5
When calculating the general lighting load for a dwelling using the NEC standard method, what unit load (VA per square foot) is applied to the gross floor area?
Question 6
GFCI protection is required for all 15A and 20A, 125V receptacles located in which of the following locations?
Question 7
A metal water pipe enters a building and is used as a grounding electrode. According to the NEC, what is the minimum length of metal water pipe that must be in contact with the earth for it to qualify as a grounding electrode?
Question 8
A concrete-encased electrode (Ufer ground) must consist of at least how many feet of bare copper wire or steel rebar encased in concrete near the bottom of a foundation footing?
Question 9
When service-entrance conductors consist of two sets of 350 kcmil copper in parallel per phase, what total cross-sectional area is used to size the supply-side bonding jumper per NEC 250.102(C)(1)?
Question 10
Interior metal gas piping in a residence must be bonded. To which of the following is it permitted to be bonded per NEC 250.104(B)?
Question 11
A dwelling unit has a gross floor area of 1,800 sq ft. Using the NEC standard method, what is the general lighting load in VA before any demand factors are applied?
Question 12
In a standard residential load calculation, what demand factor is applied to a single electric clothes dryer in a single dwelling unit?
Question 13
When applying the NEC optional calculation method for a single-family dwelling service, all load above the first 10 kVA is multiplied by what percentage?
Question 14
A 20A, 120V branch circuit supplies a single receptacle. What is the maximum continuous load that may be placed on this circuit per NEC requirements?
Question 15
The NEC requires AFCI protection for 15A and 20A, 120V branch circuits in dwelling units. Which areas of the dwelling are covered by this requirement?
Question 16
The NEC informational notes recommend limiting voltage drop on a branch circuit to what maximum percentage for satisfactory equipment operation?
Question 17
A 2,400 sq ft dwelling has a 12 kW electric range, a 5.5 kW water heater, a 5 kW dryer, a 3-ton central A/C with a 28A/240V nameplate, and a 10 kW electric heat strip. The A/C and heat strip cannot operate simultaneously. Per NEC 220.60, which load is included in the service calculation?
Question 18
A 480/277V, 3-phase, 4-wire wye service uses 500 kcmil copper ungrounded conductors. According to NEC Table 250.66, what is the minimum size copper grounding electrode conductor required?
Question 19
A 240V, single-phase motor has a full-load current (FLC) of 18A. Using NEC Table 430.52, what is the maximum rating of an inverse-time circuit breaker permitted as the branch-circuit short-circuit and ground-fault protective device?
Question 20
A feeder supplies four electric ranges with nameplate ratings of 12 kW each. Using NEC Table 220.55, what is the maximum demand load (in kW) for these four ranges?
Enable JavaScript for the interactive step-by-step quiz with instant scoring and explanations.