North Dakota Electrician Practice 18
Practice 18 for Electrician Exam learners in North Dakota: 25 questions, explained answers, and a review routine.
Free preview
These questions are for study practice only and are not official exam questions.
Preview answers are not saved as full test results.
Question 1
Question 2
Continuing: add a 5 kW dryer (220.54), an 8 kW range (220.55 Col C), and 9 kW heat (larger of noncoincident vs 6 kW A/C). The net demand at 240 V is about:
Question 3
A 2,500 A service has 7 sets of 600 kcmil copper per phase. Per NEC Table 250.66, the GEC to building steel is capped at the largest table row, which is: